1 to 16 Channel Rack Controller Pioneer 16R Model

Pioneet 16R (17K jpg)
Features
  • Simultaneous readout of 16 channels
  • 3 alarm levels per channel
  • Zero correction and stabilizing
  • software eliminates sensor drift
  • Discrete and common programmable relays
  • 4-20 mA outputs
  • Receives a wide variety of sensors
  • Accepts any 4-20 mA transmitter input
  • powered from 24 VDC
  • Input voltages: 115 / 220 VAC or 12 VDC
  • Form C, 8 Amp rated relays
  • Standard 19? rack mount
Industry Applications
  • Petrochemical plants
  • Refineries
  • Water & wastewater treatment plants
  • Pulp & paper mills
  • Gas, telephone, & electric utilities
  • Parking garages
  • Manufacturing facilities
  • Steel
  • Automotive
  • HVAC


The Pioneer™ 16R is a 19” rack mounted version of our popular Pioneer™ series of gas monitors.

This continuous monitoring controller is capable of handling up to 16 separate sensor inputs to detect gas levels from 1 to 16 remote locations. The 4 display screens on the front panel simultaneously displays the gas level for all active channels.

The Pioneer 16R includes three programmable alarm levels per channel, as well as audible and visual alarms which warn you of hazardous gas conditions. Versatile standardized plug-in cards allow a wide variety of inputs and outputs.

RKI offers the industry’s widest selection of standard and toxic gas detection sensors, which can be utilized with the Pioneer™ 16R, providing gas monitoring protection for almost any application.


Physical
Dimensions Height: 6.9” 175 mm
Width 19.0” 483 mm
Depth 12.0” 305 mm
Enclosure Standard 19” rack mount.
Wiring
Termination
Screw type terminal block 12 gauge max.
Environmental
Operating Temp 32°F to 122°F (0°C to 50°C)
Storage Temp -4°F to 158°F (-20°C to 70°C)
Relative
Humidity
0 - 95% RH non-condensing
Inputs
Direct Wired
Sensors
LEL / PPM Hydrocarbon, Oxygen
Remote amp not required for less than 500 feet.
4-20 mA Accepts any 4-20 mA transmitter (24 VDC, 2 or 3 wire, 250 mA max standard). A wide variety of RKI/Riken sensors are available with 4-20 mA signals (see List Of Detectable Gases).
Wiring distances up to 5,000 feet.
Zero Correction Zero correction and stabilizing soft-ware effectively eliminates all reasonable
sensor drift.
Sampling Methods Diffusion and sample draw heads available.
Outputs
Relays 3 relays per channel - (Alarm 1,Alarm 2, Alarm 3 or Fail)
4 common relays - (Alarm 1, Alarm 2, Alarm 3, Fail)
Single pole, double throw (SPDT) isolated contacts
Rated - 250 VAC to 8A
Individual Relay Settings: increasing or decreasing
Global Relay Settings: latching or self reset normally energized or normally de-energized time delay for alarm on and alarm off.
4-20 mA Separate current or voltage outputs for each of the 16 channels; non-isolated, 4-20 mA (into 500 ohms impedance max).
0 - 1 VDC Optional 0 to 1 VDC (into 200ohms impedance min).
24 VDC 24 VDC output provided to operate sample drawing adapters.
Display 4 alphanumeric displays with backlighting. 20 characters per line, 4 lines each (16 lines total).
Audible Internal mounted buzzer, 94 dB.
Coded output
Pulsing = Gas Alarm
Steady = Fail
Visual 5 color coded LED’s: Alarm 1, Alarm 2, Alarm 3, Pilot, and Fail.
Power 115 VAC or 12 VDC standard
Optional: 230 VAC
Battery backup option available
Controls 5 front mounted push buttons for setup and programming.
Warranty One year materials and workmanship.

Specifications subject to change without notice.